Vacuum Magnetic Contactor (VMC)
The high-voltage vacuum contactors are designed and manufactured in accordance with latest IEC standard, IEC 60470 (2000) and for indoor switchgear/controlgear purposes. The contactor shall be applied according to normal service conditions specified. Please consult other than normal service conditions.
Normal Service Conditions
- The ambient air temperature does not exceed 40°C and its average value, measured over a period of 24 h, does not exceed 35°C.
The minimum ambient air temperature is -5°C for class "minus 5 indoor". - The altitude does not exceed 1,000m.
- The ambient air is not significantly polluted by dust, smoke, corrosive or flammable gases, vapors or salt.
- The average value of relative humidity, for a period of 24h, does not exceed 95%.
The average value of relative humidity, for a period of one month, does not exceed 90%.
No condensation can be expected where sudden temperature changes occur in periods of high humidity. - Vibration due to causes external to switchgear and controlgear.
Vibration withstand 15Hz 0.2G
Shock withstand 30G - The supply voltage of auxiliary circuit shall be between 85% to 110% of rated value.
Standard
Standard List
This table can be scrolled horizontally.
Conformity to following standards | |
---|---|
IEC 60470 (2000) | International |
NEMA ICS 2-324 (1988) | U.S.A. |
JEM 1167 (1990) | Japan |
Excitation
Excitation List
This table can be scrolled horizontally.
Continuous excitation (Non-latched) | Mainly applied to frequent switching operation such as motor |
---|---|
Instantaneous excitation (Latched) | Mainly applied to non-frequent switching operation and/or to the important load which require to be contact closed even with power loss |
Protection Coordination
- The protection coordination with upper/lower stream relay shall be evaluated by considering total systems and load characteristics.
- The single-phase protection shall be provided which may be occurred by power fuses.
(Apply 2E-relay or fuse blown detector that is installed on TOSHIBA combination unit as a standard.)
Application for Surge
No surge protection will be required except for special application, however the insulation coordination shall be evaluated with following table.
Application for Surge List
This table can be scrolled horizontally.
Load | Protection | Notice |
---|---|---|
Rotating machine | Not required |
|
Dry-type transformer | Not required |
|
Oil-immersed Transformer | Not required |
|
Capacitor | Not required |
Precautions for Other Application
No surge protection will be required except for special application, however the insulation coordination shall be evaluated with following table.
- Capacitor Application
The current limiting fuses shall be combined for capacitor switching application.
The series reactor shall be connected, especially back-to-back application.
The electrical life for capacitor application will be reduced due to the high inrush current and higher recovery voltage. Please consult us. - Terminal connection
Either terminals, upper or lower, can be used for power or load side on contactor. - Control transformer
The contactor can be operated with following burden of control transformer.
Control transformer List
This table can be scrolled horizontally.
Type form of contactor | Control transformer | TOSHIBA VT |
---|---|---|
CV-6GA(L), 6HA(L) | 400VA or above | 100VA 10P10 |
CV-10HA(L), 10HB(L) | ||
CV-6KA(L) | 750VA or above |