CV-10 type
Specification
Specification List
This table can be scrolled horizontally.
TYPE FORM (*1) | Standard | CV-10HA | CV-10HAL | CV-10HB | CV-10HBL |
---|---|---|---|---|---|
Vertical terminals | CV-10HA-1 | CV-10HAL-1 | CV-10HB-1 | CV-10HBL-1 | |
Application | Motor/transformer | Capacitor | |||
Rated voltage | 12/15kV | 12kV | |||
Rated operational current | 320A | 320A | |||
Thermal current | 450A | 450A | |||
Rated frequency | 50/60Hz | ||||
Rated short-time withstand current | 5000A 1second | ||||
Rated peak withstand current | 12.5kA | ||||
Short-circuit making & breaking current | 5000/4000A | 5000A | |||
"O"- 3 min. - "CO" - 3 min. - "CO" | |||||
Rated making current (100 times) | 3200A | ||||
Rated breaking current (25 times) | 2560A | ||||
Withstand overload current | 1920A-30s | ||||
15 times 1 second | 8000A- 1s | ||||
Coordination with current-limiting fuses | Prospective short-circuit current 40kA | ||||
Cut-off current (Peak) | 50kA | ||||
Insulation level | Impulse withstand | 75kV | |||
Power frequency withstand | 28kV | ||||
Rated duties (40% on load factor) | 300 op/hr | 120 op/hr | 300 op/hr | 120 op/hr | |
Endurance | Mechanical life | 2.5 million operations | 0.25 million operations | ||
Electrical life (AC3) | 0.25 million operations (AC3) | 0.25 million operations (AC3) | |||
Maximum applicable load capacity | Motor | 3500kW | - | ||
Transformer | 4500kVA | - | |||
Capacitor | - | 5000kVar |