Large-size series [type1/type2]
Large-size series [type1/type2]
Controller
Controller List
This table can be scrolled horizontally.
Item | For electric control (type 1) | For instrumentation (type 2) | |
---|---|---|---|
Program capacity | 256 K steps | 512 K steps | |
Local variable/global variable | 256 K words | 256 K words | |
I/O variable | 16 K words | 16 K words | |
Tag | - | Standard input/output (process alarm management) Toshiba HMI/OIS-DS interface |
|
Task | Periodical task | Ultra high speed: 0.5 to 500 ms High speed: 0.5 to 500 ms RIO: 0.5 to 500 ms Main: 0.5 to 1,000 ms |
High speed: 10 to 500 ms Main: 100 to 10,000 ms |
Event task | Event: 8 or I/O interruption: 16: Selective | Event: 8 I/O interruption: 16 | |
Task switching time | 60 μs or less | ||
Processing performance |
Bit Contact: 20 ns Integer Transfer: 20 ns,Addition/subtraction: 20 ns Floating point Addition: 120 ns, Multiplication: 120 ns |
||
Programming Language | Four languages conformed with IEC 61131-3 standard LD (Ladder Diagram) FBD (Function Block Diagram) SFC (Sequential Function Chart) ST (Structured Text) |
Supervisory Control Network
supervisory Control Network / 1 Gbps Ethernet List
This table can be scrolled horizontally.
Item | Specifications |
---|---|
Topology | Star wiring |
Ethernet frame | DIX type |
No. of nodes | 254 maximum/system (single transmission line) |
No. of repeater hubs | 10BASE-T: 4 maximum (serial connection) |
10BASE-TX: 2 maximum (serial connection) | |
1000BASE-T: 1 maximum | |
No. of LAN switches | No limits on the number of connecting switches |
No. of Ethernet modules to be installed | 4 transmission modules maximum |
Inter-Controller Network / Real-Time Ethernet TC-net 100 List
Item | Specifications |
---|---|
Hub-to-station distance | 2 km |
Cable | Multi-mode optical fiber |
Configuration | Single transmission line/dual transmission line |
Topology | Star wiring |
Transmission mode | Scan transmission:
|
Scan transmission capacity | 128 KW/system 2,048 blocks/system (64 W/block) Transmission capacity/node
|
Status change detection | Number of status change detecting words: 128 KW Change detecting cycle: Number of detecting words x 30 μs Detecting signal intervals: 50 ms or more |
No. of connecting nodes | 254 maximum/system |
High-Speed Serial I/O System / TC-net I/O
High-Speed Serial I/O System / TC-net I/O List
This table can be scrolled horizontally.
Item | Electrical | Optical |
---|---|---|
Topology | Duplex loop (transmission, reception) | |
Duplex loop (transmission, reception) | 100 Mbps | |
I/O interface | 32 nodes/loop | |
Topology | 16 modules/node | |
Transmission cable | Category 5 twisted-pair cable with shield | Optical fiber cable GI 50/125 |
Maximum cable length | 10 m | 2 km |
Overall cable length | 100 m maximum | 4 km maximum |
Scan cycle | High-speed scan: 100 μs or more Medium-speed scan: 1 ms or more |
|
Redundancy | Detour control in case of transmission line disconnections Duplex configuration of duplex loops available |
- * Microsoft ® , Windows, Windows Vista and Windows Server are either registered trademarks or trademarks of Microsoft Corporation of the United States and/or other countries.
- * The formal name of Windows is Microsoft Windows Operating System.
- * TC-net is a registered trademark of Toshiba Corporation.
- * Other company names and product names herein are trademarks or registered trademarks of the companies concerned.
- * The contents are subject to change without notice for design changes or other reasons.